Turbine - Generator on-Line Diagnostics Using RF Monitoring
- 1 December 1981
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Apparatus and Systems
- Vol. PAS-100 (12) , 4974-4982
- https://doi.org/10.1109/TPAS.1981.316465
Abstract
An EPRI-Westinghouse funded program to develop turbine-generator on-line diagnostics through monitoring of a generator's neutral radio frequency current has produced an on-line RF monitor. It is designed to detect internal generator arcing and alert the operator if the arcing level becomes destructively high.Keywords
This publication has 2 references indexed in Scilit:
- On Line Incipient ARC Detection in Large Turbine Generator Stator WindingIEEE Transactions on Power Apparatus and Systems, 1980
- Radio Frequency Sensing of Incipient Arcing Faults within Large Turbine GeneratorsIEEE Transactions on Power Apparatus and Systems, 1979