Dielectric Tests for EHV Transformers
- 1 January 1968
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Apparatus and Systems
- Vol. PAS-87 (1) , 135-145
- https://doi.org/10.1109/tpas.1968.292264
Abstract
Specific proposals for revision of dielectric tests for EHV power transformers are made. An objective is improved operating reliability by specifying tests which are more compatible with service requirements. Impulse and switching surge tests are coordinated independently with lightning arrester characteristics. Low-frequency tests are disassociated from transient voltage requirements and are related to operating voltage only. Low-frequency test voltages are reduced and their duration is increased; absence of corona during the test is required. Suggestions for further development work are made.Keywords
This publication has 14 references indexed in Scilit:
- Switching Surge Tests For Oil-Insulated Power TransformersIEEE Transactions on Power Apparatus and Systems, 1967
- Transformer Corona TestingIEEE Transactions on Power Apparatus and Systems, 1966
- Tests for Damaging Corona for Oil-Insulated Power TransformersIEEE Transactions on Power Apparatus and Systems, 1966
- Switching Surge Testing of TransformersIEEE Transactions on Power Apparatus and Systems, 1966
- Power Transformers and Corona TestingIEEE Transactions on Power Apparatus and Systems, 1965
- Corona Measurement on High-Voltage Apparatus Using the Bushing Capacitance TapIEEE Transactions on Power Apparatus and Systems, 1965
- Ultrasonic Corona Detection in TransformersIEEE Transactions on Power Apparatus and Systems, 1965
- Reduced Insulation in Power Systems at the Higher Voltages-The Problems It Presents [includes discussion]Transactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems, 1956
- A Study of the Coordination or Modern Arresters and Transformer Insulation [includes discussion]Transactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems, 1956
- Corona Voltages of Typical Transformer Insulations Under OilTransactions of the American Institute of Electrical Engineers, 1938