Lightning Performance of Double-Circuit Transmission Lines
- 1 May 1970
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Apparatus and Systems
- Vol. PAS-89 (5) , 913-925
- https://doi.org/10.1109/tpas.1970.292654
Abstract
This paper presents further studies of lightning outage rates on double-circuit transmission lines. Satisfactory agreement with field data has been demonstrated for calculations of total and double-circuit outage rates and for prediction of outage types on high-voltage lines. An analysis of the parameters influencing double- circuit outage rates has enabled proposal of several line designs that should achieve a low proportion of lightning faults involving both circuits. Two configurations are of particular interest-a double-horizontal arrangement with one circuit above the other, and a double-triangular arrangement utilizing a conventional lattice tower with three crossarms.Keywords