Factors concerned in the efficient steam sterilization of surgical dressings
Open Access
- 1 September 1961
- journal article
- research article
- Published by BMJ in Journal of Clinical Pathology
- Vol. 14 (5) , 505-511
- https://doi.org/10.1136/jcp.14.5.505
Abstract
Some of the factors affecting the efficient steam sterilization of dressings have been examined. A jacketed sterilizer will process a load more quickly than a sterilizer without a jacket. The level of fore-vacuum is critical and must reach an absolute pressure of 20 mm. Hg (29·2 in.Hg vacuum) or less. This will overcome all conditions of overpacking studied. The level of after-vacuum should be 100 mm. Hg absolute or less, preferably near 50 mm. Hg absolute. Overpacking cannot be defined in terms of weight of a fabric per unit volume of container but occurs when a load is compressed in its container.Keywords
This publication has 7 references indexed in Scilit:
- A survey of some problems in sterilizationJournal of Clinical Pathology, 1961
- A SMALL AUTOCLAVE IN A LARGE HOSPITALThe Lancet, 1960
- VACUUM DRYING OF STEAM STERILIZED DRESSINGSJournal of Applied Bacteriology, 1958
- Influence of Initial Vacuum on Steam Sterilization of DressingsBMJ, 1958
- Principles and Methods of SterilizationThe American Journal of Nursing, 1957
- Gravity air-displacement pressure steam sterilisers; simple repair of some common defects.1957
- LABORATORY TESTS OF OPERATING-THEATRE STERILISERSThe Lancet, 1956