Ventilation Efficiencies of Desk-Mounted Task/Ambient Conditioning Systems
- 1 December 1999
- journal article
- Published by Hindawi Limited in Indoor Air
- Vol. 9 (4) , 273-281
- https://doi.org/10.1111/j.1600-0668.1999.00007.x
Abstract
In laboratory experiments, we investigated two task/ambient conditioning systems with air supplied from desk‐mounted air outlets to efficiently ventilate the breathing zone of heated manikins seated at desks. In most experiments, the task conditioning systems provided outside air while a conventional ventilation system provided additional space cooling but no outside air. Air change effectiveness (i.e., exhaust air age divided by age of air at the manikin's face) was measured with a tracer gas step‐up procedure. Other tracer gases simulated the release of pollutants from nearby occupants and from the floor covering, and the associated pollutant removal efficiencies (i.e., exhaust air concentrations divided by concentrations at manikin's face) were calculated. High values of air change effectiveness (∼1.3 to 1.9) and high values of pollutant removal efficiency (∼1.2 to 1.6) were measured when these task conditioning systems supplied 100% outdoor air at a flow rate of 7 to 9 L s‐1 per occupant. Air change effectiveness was reasonably well correlated with the pollutant removal efficiency. Overall, the experimental data suggest that these task/ambient conditioning systems can be used to improve ventilation and air quality or to save energy while maintaining a typical level of IAQ at the breathing zone.Keywords
This publication has 5 references indexed in Scilit:
- Air Change Effectiveness and Pollutant Removal Efficiency during Adverse Mixing ConditionsIndoor Air, 1997
- Indoor airflow and pollutant removal in a room with floor-based task ventilation: Results of additional experimentsBuilding and Environment, 1995
- Indoor Air Flow and Pollutant Removal in a Room with Task VentilationIndoor Air, 1991
- Testing of Localized Ventilation Systems in a New Controlled Environment ChamberIndoor Air, 1991
- The use of moments for assessing air quality in ventilated roomsBuilding and Environment, 1983