Events Associated with Zero Current Passage during the Rapid Commutation of a Vacuum Arc
- 1 January 1983
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Plasma Science
- Vol. 11 (3) , 181-188
- https://doi.org/10.1109/tps.1983.4316248
Abstract
Events associated with the rapid commutation of the current in a diffuse vacuum arc are explored experimentally and analytically in the short interval during which the current is brought to zero and the recovery voltage is established across the residual plasma. A brief pause of the order of 100 ns is observed between the passage of current through zero and the point where the recovery voltage starts to rise. Current zero is interpreted as the instant when the ion and electron currents are equal. During the subsequent pause the electrons are brought to rest and only then does a positive ion sheath develop, allowing voltage to build up across it. The charge remaining in the gap at current zero is observed to depend on the initial steady-state current and the rate at which the current is ramped to zero. Qualitative agreement is obtained by analysis, but the decay of the charge residue appears to be more rapid than the analysis predicts.Keywords
This publication has 6 references indexed in Scilit:
- Recovery Times of Vaccum Interrupters Which have Stationary Anode SpotsIEEE Transactions on Power Apparatus and Systems, 1982
- A Model for DC Interruption in Diffuse Vacuum ArcsIEEE Transactions on Plasma Science, 1980
- Erosion products from the cathode spot region of a copper vacuum arcJournal of Applied Physics, 1978
- Sheath Growth in a Low Pressure PlasmaPhysics of Fluids, 1971
- High-current vacuum arcs. Part 1: An experimental studyProceedings of the Institution of Electrical Engineers, 1970
- Analysis of the Electrode Products Emitted by dc Arcs in a Vacuum AmbientJournal of Applied Physics, 1969