Addition of Olfs from Different Pollution Sources, determined by a Trained Panel

Abstract
The purpose of this study was to predict how indoor air is perceived when polluted by different materials simultaneously. A panel of five trained judges was exposed to air polluted by each of 11 different single pollution sources. The panel was also exposed to 13 pair combinations of these single pollution sources and to one combination of five sources. The pollution sources comprised typical indoor building materials, materials from ventilation systems and other frequently occurring indoor pollution sources. The results indicate that the total sensory pollution load in a space may, as a first approximation, be predkted by simple addition of the olf values of the single sources.