Influence of harmonics on power distribution system protection
- 1 April 1988
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 3 (2) , 549-557
- https://doi.org/10.1109/61.4292
Abstract
The effects of nonsinusoidal voltages and currents on the performance of static underfrequency and overcurrent relays are experimentally studied. The tests were conducted in such a way that the frequency, amplitude and phase shift of individual harmonics could be adjusted in a controlled manner by using a waveform generator with a phase-locking circuit. The relationship between the harmonic currents and voltages was modeled in terms of the power system impedance within residential distribution systems. It was found that for harmonic voltage and current amplitudes (as they occur in distribution systems), underfrequency relays and the time delay operation of overcurrent relays show a marked deterioration in performance. The instantaneous operating characteristics of overcurrent relays, however, are hardly affected by the presence of harmonic currents.<>Keywords
This publication has 5 references indexed in Scilit:
- Aging of Electrical Appliances Due to Harnmonics of the Power System's VoltageIEEE Transactions on Power Delivery, 1986
- Vibration and current monitoring for detecting airgap eccentricity in large induction motorsIEE Proceedings B Electric Power Applications, 1986
- The Effect of Harmonics on the Operating Points of Electromechanical RelaysIEEE Transactions on Power Apparatus and Systems, 1985
- Bibliography of Relay Literature, 1982-1983IEEE Transactions on Power Apparatus and Systems, 1985
- The Impact of Sine-Wave Distortions on Protective RelaysIEEE Transactions on Industry Applications, 1984