Development and Testing of an Electro-Mechanical Relay to Detect Fallen Distribution Conductors
- 1 June 1982
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Apparatus and Systems
- Vol. PAS-101 (6) , 1643-1650
- https://doi.org/10.1109/TPAS.1982.317214
Abstract
If undetected by phase or ground overcurrent relaying methods, fallen distribution conductors or high impedance faults may be a fire hazard and a threat to public safety. Four promising relay schemes to detect these faults are evaluated using both digital and analog techniques and one scheme was chosen for prototype construction. In the light of economic and performance data, a prototype Ratio Ground Relay has been constructed for installation and testing on six Pennsylvania Power and Light distribution feeders.Keywords
This publication has 1 reference indexed in Scilit:
- Detection of High Impedance Faults on Multi-Grounded Primary Distribution SystemsIEEE Transactions on Power Apparatus and Systems, 1981