Legionella pneumophila in a hospital water system following a nosocomial outbreak: prevalence, monoclonal antibody subgrouping and effect of control measures
- 1 June 1987
- journal article
- research article
- Published by Cambridge University Press (CUP) in Epidemiology and Infection
- Vol. 98 (3) , 253-262
- https://doi.org/10.1017/s0950268800062002
Abstract
SUMMARY: Swabs and water samples from a hospital water system were cultured for legionellae over an extended period. Legionella pneumophila serogroup 1, including outbreak associated strains, were isolated in small numbers from approximately 5% of these samples despite implementation of the current DHSS/Welsh Office regulations. No cases of nosocomial legionnaires' disease were proven during the study. Physical cleaning and chemical sterilization of taps, and replacement of washers with ‘approved’ brands did not eradicate the organisms. Eradication of legionellae in hospital water supplies appears to be unnecessary in preventing nosocomial legionnaires' disease provided the current DHSS/Welsh Office recommendations are implemented.This publication has 12 references indexed in Scilit:
- Legionnaires' disease cluster and reduction in hospital hot water temperatures.BMJ, 1986
- Legionella pneumophilaserogroup 1 subgrouping by monoclonal antibodies – an epidemiological toolEpidemiology and Infection, 1985
- WATER FITTINGS AS SOURCES OF LEGIONELLA PNEUMOPHILA IN A HOSPITAL PLUMBING SYSTEMThe Lancet, 1984
- Legionnaires' Disease Associated with a Hospital Water System: A Cluster of 24 Nosocomial CasesAnnals of Internal Medicine, 1983
- LEGIONELLA PNEUMOPHILA IN HOSPITAL HOT WATER CYLINDERSThe Lancet, 1982
- LEGIONELLA PNEUMOPHILA IN WATER PLUMBING SYSTEMSThe Lancet, 1982
- POTABLE WATER SUPPLY AS THE HOSPITAL RESERVOIR FOR PITTSBURGH PNEUMONIA AGENTThe Lancet, 1982
- INVESTIGATION AND CONTROL OF AN OUTBREAK OF LEGIONNAIRES' DISEASE IN A DISTRICT GENERAL HOSPITALThe Lancet, 1981
- LEGIONNAIRES' DISEASE IN A TRANSPLANT UNIT: ISOLATION OF THE CAUSATIVE AGENT FROM SHOWER BATHSThe Lancet, 1980