Final Report on the Clean Fog Test for HVAC Insulators
- 1 October 1987
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 2 (4) , 1317-1326
- https://doi.org/10.1109/tpwrd.1987.4308259
Abstract
The results of a program of tests carried out in a number of laboratories on artificially contaminated insulators using the clean fog method are reported and analyzed. The effects of fog generation characteristics, insulator coating variability, and calculation method are considered. The analysis shows that a high level of reproducibility can be achieved. Requirements are given for ensuring that the reproducibility and repeatability of the method are adequate for its acceptance as a standard testing procedure.Keywords
This publication has 3 references indexed in Scilit:
- The AC Clean-Fog Test for Contaminated Insulators Prepared by the Task Force Members on Testing IEEE Insulators, IEEE Working Group on Insulator Contamination, Lightning and Insulator SubcommitteeIEEE Power Engineering Review, 1983
- Method of Maximum Likelihood Applied to the Analysis of Flashover DataIEEE Transactions on Power Apparatus and Systems, 1969
- A Method for Obtaining and Analyzing Sensitivity DataJournal of the American Statistical Association, 1948