Phase-to-phase insulation part I: Generalized effects of stress parameters and gap geometry
- 1 March 1976
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Apparatus and Systems
- Vol. 95 (2) , 643-650
- https://doi.org/10.1109/t-pas.1976.32146
Abstract
The parameters determining the response of phase-to-phase insulation are the amplitudes Vn(negative) and Vp(positive) of the two voltage components to the ground, their shape and the relative displacement Δt of their crests. In the present paper, the effects of Δt and of the ratio α = Vn/(Vn+ Vp) on the virtual total breakdown voltage Vn+ Vpare investigated. An attempt is made to derive an analytical expression for the combined effect of α, Δt and the polarity of the two components. Recommendations are offered as to the required geometrical arrangement for performing phase-to-phase tests as well as to the presentation of their results.Keywords
This publication has 5 references indexed in Scilit:
- Coefficient of Variation of the Positive-Impulse Breakdown of Long Air-GapsIEEE Transactions on Power Apparatus and Systems, 1974
- Phase-To-Ground and Phase-To-Phase Switching-Surge Flashover of External Insulation of UHV StationsIEEE Transactions on Power Apparatus and Systems, 1974
- Estimating the Switching-Surge Performance of Transmission LinesIEEE Transactions on Power Apparatus and Systems, 1970
- Strength Characteristics of Air Gaps Subjected to Interphase Switching SurgesIEEE Transactions on Power Apparatus and Systems, 1970
- Phase-Phase and Phase-Neutral Switching Surges on 500-kV Open-Ended LinesIEEE Transactions on Power Apparatus and Systems, 1969