Corona performance of a conductor bundle for bipolar HDVC transmission at plusminus 750 kV
- 1 November 1977
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Apparatus and Systems
- Vol. 96 (6) , 1872-1881
- https://doi.org/10.1109/t-pas.1977.32521
Abstract
As part of an overall study on the corona performance of bipolar HVDC transmission lines between ± 600 kV and ± 1200 kV, the corona performance of a 4 × 1.6 in. conductor bundle has been studied on an outdoor test line at a nominal voltage of ± 750 kV. The conductor bundle has been tested over a period of about six months covering summer, fall and winter conditions. The study included long-term measurements at ± 750 kV as well as periodic measurements at varying voltages between ± 600 kV and ± 900 kV and at monopolar voltages of + 750 kV and - 750 kV. The principal parameters measured are radio interference (RI), corona losses (CL) and audible noise (AN). Some measurements of ion current density at ground level have also been made. An analysis of the test results is presented in this paper showing the statistical corona performance of the conductor bundle on an annual basis, the generating quantities of RI, CL and AN as functions of the maximum bundle conductor gradient * , frequency spectra and lateral profiles of RI and AN.Keywords
This publication has 7 references indexed in Scilit:
- A Comparative Study of the Corona Performance of Conductor Bundles for 1200 KV Transmission LinesIEEE Transactions on Power Apparatus and Systems, 1974
- The Use of Single-Phase Overhead Test Lines and Test Cages to Evaluate the Corona Effects of EHV and UHV Transmission LinesIEEE Transactions on Power Apparatus and Systems, 1974
- Propagation Analysis of HF Currents and Voltages on Lossy Power LinesIEEE Transactions on Power Apparatus and Systems, 1973
- Electrostatic Field of a System of Parallel Cylindrical ConductorsIEEE Transactions on Power Apparatus and Systems, 1969
- The Apple Grove 750-kV Project-775-kV Radio Influence and Corona Loss InvestigationsIEEE Transactions on Power Apparatus and Systems, 1965
- The Spectrum of Corona Noise near a Power Transmission LineTransactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems, 1961
- Radio Interference Studies on Extra-High-Voltage LinesTransactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems, 1961