Isolation of Legionella species from drinking water
- 1 October 1984
- journal article
- research article
- Published by American Society for Microbiology in Applied and Environmental Microbiology
- Vol. 48 (4) , 830-832
- https://doi.org/10.1128/aem.48.4.830-832.1984
Abstract
Three different species of Legionella were recovered from samples of water taken from chlorinated public water supplies where no coliform bacteria were simultaneously detected. Five of 856 samples yielded Legionella isolates. Three isolates were identified as Legionella pneumophila serogroup 1, the fourth was identified as Legionella dumoffii, and the fifth was identified as Legionella jordanis. Studies to determine the survival of L. pneumophila Flint 1 serogroup 1 in tap water at various temperatures and in tap water with added sodium hypochlorite were done. These organisms were found to survive for 299 days in tap water at 24 and 5 degrees C but not at 35 degrees C. A concentration of at least 0.2 mg of residual chlorine per ml was required to eliminate at least 90% of L. pneumophila and Escherichia coli inocula in 2 h.This publication has 9 references indexed in Scilit:
- Legionella oakridgensis: unusual new species isolated from cooling tower waterApplied and Environmental Microbiology, 1983
- Glycine-containing selective medium for isolation of Legionellaceae from environmental specimensApplied and Environmental Microbiology, 1981
- Isolation of Legionella pneumophila from water systems: methods and preliminary results.BMJ, 1981
- Isolation of Legionella pneumophila from Hospital Shower HeadsAnnals of Internal Medicine, 1981
- Legionella gormanii sp. novJournal of Clinical Microbiology, 1980
- Pittsburgh Pneumonia Agent: Direct Isolation from Human Lung TissueThe Journal of Infectious Diseases, 1980
- Isolation of the Legionnaires' Disease Bacterium from Environmental SamplesAnnals of Internal Medicine, 1979
- A Major Focus of Legionnaires' Disease in Bloomington, IndianaAnnals of Internal Medicine, 1979