The Salt Fog Test and its Use in Insulator Selection for Polluted Localities
- 1 November 1973
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Apparatus and Systems
- Vol. PAS-92 (6) , 1876-1887
- https://doi.org/10.1109/tpas.1973.293567
Abstract
After describing briefly the salt fog test, the authors show, by means of comparisons between laboratory results and results obtained in natural environments. that the behaviour of insulators in salt fog is very similar to their behaviour in representative types of natural conditions. Having thus established that the salt fog test is representative, the paper derives certain fundamental rules relating to the behaviour of insulators in salt fog as a function of their geometrical and surface characteristics. The importance of such rules is stressed in relation to the choice, on a quantitative basis, of insulators for areas with different degrees of pollution and suggestions are made as to the criteria and methods to adopt for classifying such areas.Keywords
This publication has 7 references indexed in Scilit:
- How to Choose Insulators for Polluted AreasIEEE Transactions on Power Apparatus and Systems, 1973
- Control of insulator contamination in substationsJournal of the Franklin Institute, 1972
- Anti-Pollution Design Criteria for Line and Station InsulatorsIEEE Transactions on Power Apparatus and Systems, 1972
- Effect of pollution on high-voltage outdoor insulatorsProceedings of the Institution of Electrical Engineers, 1971
- Artificial- and natural-pollution tests on outdoor 400 kV substation insulatorsProceedings of the Institution of Electrical Engineers, 1971
- The Measurement in the Field of Pollution by DustJournal of Occupational and Environmental Medicine, 1965
- Artificial-pollution test for high-voltage outdoor insulatorsProceedings of the Institution of Electrical Engineers, 1964