DC System Resonance Analysis
- 1 January 1987
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 2 (1) , 156-164
- https://doi.org/10.1109/tpwrd.1987.4308086
Abstract
DC filters and dc smoothing reactors are primarily designed to meet performance requirements with regard to telephone interference levels and commutation failure frequency. Other factors, however, place constraints on the size of the dc filter capacitance and the smoothing reactor inductance. The principal constraint is the avoidance of resonance conditions on the dc side at a low order harmonic of the commutating voltage. This paper discusses the factors which must be considered when analyzing dc side resonance. Specific considerations for the Intermountain Power Project are given.Keywords
This publication has 4 references indexed in Scilit:
- DC filter design methods for HVDC systemsIEEE Transactions on Power Apparatus and Systems, 1977
- Power Transmission by Direct CurrentPublished by Springer Nature ,1975
- Transient Overvoltages Caused by Monopolar Ground Fault on Bipolar DC Line: Theory and SimulationIEEE Transactions on Power Apparatus and Systems, 1970
- Transient Overvoltage on a Bipolar HVDC Overhead Line Caused by DC Line FaultsIEEE Transactions on Power Apparatus and Systems, 1970