Pollution and rain flashovers on HVDC wall bushings
- 6 January 2003
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 29-32 vol.1
- https://doi.org/10.1109/icpadm.1988.38323
Abstract
Measurements carried out on a large wall bushing are described. They show that uneven rain distribution can cause flashovers even at very low pollution levels. A possible mechanism for these rain flashovers is proposed. It is reported that water-repellent surfaces provide an efficient remedy for this type of flashover.Keywords
This publication has 2 references indexed in Scilit: