Supply to arc furnaces: measurement and prediction of supply-voltage fluctuation
- 1 January 1972
- journal article
- Published by Institution of Engineering and Technology (IET) in Proceedings of the Institution of Electrical Engineers
- Vol. 119 (4) , 456-465
- https://doi.org/10.1049/piee.1972.0099
Abstract
In the electric-arc furnace, arc motion and other factors cause a large irregular fluctuation of current. This fluctuating load results in a fluctuation of the supply voltage, which can cause annoying flicker in lamps connected to the system. The best short-term measure of the flicker severity of this voltage fluctuation is the r.m.s. value of the envelope with which the fluctuation modulates the supply-voltage wave. An instrument which indicates and records this r.m.s. voltage is described. To assess the long-term severity of the voltage fluctuation (whose amplitude varies widely during a complete furnace-operating cycle), a probabilistic method has been developed, based on a quantity called the gauge-point voltage fluctuation. Methods of estimating this quantity during the design stage of supplies to arc-furnace installations are described, including supplies to multifurnace installations. The limits for gauge-point voltage fluctuation in use in Great Britain are specified and the reasons for their choice discussed. Some comparison is made with earlier investigations in Great Britain and abroad.Keywords
This publication has 0 references indexed in Scilit: