Impact of Heating and Air Conditioning System Operation and Leakage on Ventilation and Intercompartment Transport: Studies in Unoccupied and Occupied Tennessee Valley Homes
- 1 February 1990
- journal article
- research article
- Published by Taylor & Francis in Journal of the Air & Waste Management Association
- Vol. 40 (2) , 194-198
- https://doi.org/10.1080/10473289.1990.10466676
Abstract
Forced-air heating and air conditioning (HAC) systems caused an average and maximum increase in air infiltration rates of 1.8- and 4.3-fold, respectively, during brief whole-house studies of tracer gas decay In 39 occupied houses. An average Increase in air infiltration rate of 0.33 ± 0.37 h−1 corresponded to an Incremental air leak of 240 m3/h, based on approximate house volume. More detailed tracer gas decay studies were performed in basement, kitchen and bedroom locations of six homes with low air infiltration rates (i.e., −1). The HAC mixed the indoor air efficiently between measurement sites. HAC operation also caused 1.1- to 3.6-fold increases in air infiltration rates, corresponding to absolute increases of 0.02 to 0.1 h-1. In an unoccupied research house, three-fold increases in average air infiltration rate with HAC operation (i.e., from 0.13 to 0.36 h−1) were reduced to two-fold (i.e., from 0.10 to 0.18 h−1) by sealing the external HAC unit and crawlspace ductwork system. This sealing also resulted in a 30 percent reduction in crawlspace-to-indoor transport rates with the HAC turned on. Blower door tests indicated a <20 percent reduction in house leakage area.This publication has 0 references indexed in Scilit: