A bacteriological evaluation of laminar-flow systems for orthopaedic surgery
- 1 June 1973
- journal article
- research article
- Published by Cambridge University Press (CUP) in Epidemiology and Infection
- Vol. 71 (3) , 559-564
- https://doi.org/10.1017/s0022172400046544
Abstract
SUMMARY An evaluation has been undertaken of the efficiency of laminar-flow ventilation in operating-rooms in which conventional operating-room clothing was used. It has been demonstrated that velocities in the region of 0·3–0·4 m/sec. will give maximum returns for effort in both down-flow and cross-flow systems. At this velocity the laminar-flow system, in terms of airborne bacteria measured at the would site, was about 11 times more effients using horizontal air-flow and 35–90 times more efficient using vertical air-flow than a plenum-ventilated operating room.Keywords
This publication has 4 references indexed in Scilit:
- AN EXPERIMENTAL LAMINAR-FLOW OPERATING-ROOMThe Lancet, 1971
- LAMINAR/LINEAR FLOW SYSTEM OF VENTILATION: Its Application to Medicine and SurgeryThe Lancet, 1970
- Postoperative wound infection.1956