More than 300 residents of a private high-rise housing estate were infected with severe acute respiratory syndrome within a short period during the 2003 epidemic in Hong Kong. The outbreak occurred after the identified index patient visited a flat on a middle floor in Block E of the Amoy Gardens estate on two nights. Approximately 45% of the subsequently infected people resided in Block E, while the other 55% of infected cases mainly resided in six other blocks close to Block E. The distribution of the infected flats in Block E conformed to a non-uniform spatial pattern. Probable environmental causes for airborne transmission associated with the air movements between flats in Block E are identified. The well-established multi-zone airflow modeling method was used to analyze the virus-laden bio-aerosol dispersion between flats through door and window leakage areas in Block E under six different scenarios. The distribution of infection risk in Block E matched with the virus concentrations in flats predicted with the use of multi-zone modeling. Our study shows the importance of ventilation design in high-rise residential apartments.Keywords
This publication has 13 references indexed in Scilit:
- Risk of indoor airborne infection transmission estimated from carbon dioxide concentrationIndoor Air, 2003
- Possible role of an animal vector in the SARS outbreak at Amoy GardensThe Lancet, 2003
- A Major Outbreak of Severe Acute Respiratory Syndrome in Hong KongNew England Journal of Medicine, 2003
- Clinical progression and viral load in a community outbreak of coronavirus-associated SARS pneumonia: a prospective studyThe Lancet, 2003
- VENTILATION OF BUILDINGSPublished by Taylor & Francis ,2002
- Influence of a depth of a recessed space to flow due to air-conditioner heat rejectionEnergy and Buildings, 2002
- Spread and prevention of some common viral infections in community facilities and domestic homesJournal of Applied Microbiology, 2001
- Effect of building re-entrant shape on performance of air-cooled condensing unitsEnergy and Buildings, 2000
- Prediction of natural ventilation in buildings with large openingsBuilding and Environment, 2000
- Multi-zone dispersal analysis by element assemblyBuilding and Environment, 1989