An investigation of operating theatre staff exposed to humidifier fever antigens.
Open Access
- 1 May 1981
- journal article
- research article
- Published by BMJ in Occupational and Environmental Medicine
- Vol. 38 (2) , 144-151
- https://doi.org/10.1136/oem.38.2.144
Abstract
Sixty staff working in a hospital operating theatre, where a case of humidifier fever had been identified, were studied together with 49 subjects working in other parts of the hospital. They each had a blood test for serology, a skin test, and a chest radiograph and completed a questionnaire. The theatre staff also had pulmonary function tests. The theatre humidifier was found to contain several organisms including amoebae and antigens cross-reacting highly with those implicated in previous outbreaks of humidifier fever. Of the 60 exposed subjects, 25 had developed antibodies, nine had probable symptoms of humidifier fever, and six possible symptoms. There was a strong association between symptoms and antibodies (p = 6 x 10(-5) by Fisher's exact test). The development of antibodies was also related to duration of exposure in the theatre (p less than 0.01 by X2 test for trend) and inversely to smoking (p = 0.0073 by Fisher's exact test) but not to history of atopy. Because of the presence of antigens and because certain biocides added were ineffective in controlling antigenic build-up the humidifier was switched off. Eight months later specific IgG levels in the theatre staff sera, estimated by an enzyme-linked immunosorbent assay technique, had fallen on average by 25%. Inhalation challenge with humidifier water was performed in eight subjects. Four subjects reacted to the challenge, including both those with antibodies and previous symptoms.Keywords
This publication has 20 references indexed in Scilit:
- Microbial and immunological investigations and remedial action after an outbreak of humidifier feverOccupational and Environmental Medicine, 1980
- Humidifier fever in an operating theatre.BMJ, 1979
- Humidifier feverThorax, 1977
- EXTRINSIC ALLERGIC ALVEOLITIS AND CONTAMINATED COOLING-WATER IN A FACTORY MACHINEThe Lancet, 1977
- Protozoa as sources of antigen in ‘humidifier fever’Nature, 1976
- Chronic hypersensitivity lung disease with recurrent episodes of hypersensitivity pneumonitis due to a contaminated central humidifierClinical and Experimental Allergy, 1976
- Chest symptoms in farming communities with special reference to farmer's lung.Occupational and Environmental Medicine, 1975
- Characterization of thermophilic actinomycetes isolated from residential heating and humidification systemsJournal of Allergy and Clinical Immunology, 1973
- Hypersensitivity pneumonitis due to contamination of home humidifierJournal of Allergy and Clinical Immunology, 1972
- Hypersensitivity pneumonitis related to a home furnace humidifierJournal of Allergy and Clinical Immunology, 1971