Transformer Diagnostic Testing by Frequuency Response Analysis
- 1 November 1978
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Apparatus and Systems
- Vol. PAS-97 (6) , 2144-2153
- https://doi.org/10.1109/tpas.1978.354718
Abstract
Winding deformation in power transformers can be measured externally using a new frequency response analysis (FRA) method Field experience since 1975, on five separate transformers up to 550 MVA rating, 230kVclassindicatesthatthismethod hasadvantagesover the low voltage impulse (LVI) method as a practical maintenance tool. Results on suspect transformers indicate that benchmark reference data is not always necessary to identify certain kinds of mechanical damage.Keywords