Corona Loss Measurements for the Design of Transmission Lines to Operate at Voltages Between 220 Kv. and 330 Kv.
- 1 March 1933
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in Transactions of the American Institute of Electrical Engineers
- Vol. 52 (1) , 55-62
- https://doi.org/10.1109/t-aiee.1933.5056251
Abstract
Corona loss measurements were obtained on conductors of three different diameters; namely, 1.125 in., 1.49 in. and 2.0 in. Voltages up to 600-kv. line voltage were used in these measurements. Various surface conditions of the 1.125-in. cable were studied. These measurements include tests on the new cable as received, the cable as washed, scratch brushed, buffed and dragged. The aging of the dragged cable was observed for seven months. Data were obtained on the daily variation of loss. The effects of configuration and transposition were studied on No. 22 wire. A description of the modifications in the high-voltage wattmeter for these high-voltage measurements is reported.Keywords
This publication has 3 references indexed in Scilit:
- Corona Energy Loss Influence of Surface Conditions as Affecting Corona Energy Loss From High-Voltage Transmission LinesTransactions of the American Institute of Electrical Engineers, 1932
- Corona Loss Measurements on a 220-Kv. 60-Cycle Three-Phase Experimental LineTransactions of the American Institute of Electrical Engineers, 1931
- The Hysteresis Character of Corona FormationTransactions of the American Institute of Electrical Engineers, 1924