Abstract
A scheme for improving reliable operation of a PID governor of a hydraulic turbine generating unit is proposed. The parameters of governor and actuators are identified on-line to, a) detect their anomalous behaviours, b) facilitate the calibration of the proportional integral and derivative gain settings. An adaptive filter is used to detect the lightly damped oscillations of the system. The proposed scheme was verified via simulation on the real data obtained from one of Mactaquac hydro-generating units of New Brunswick Electrical Power Commission. The simulation results show that the proposed scheme can indeed provide an accurate and rapid detection of the abnormal system operations.

This publication has 9 references indexed in Scilit: