Occurrence and pathogenicity of Naegleria fowleri in artificially heated waters
- 1 March 1983
- journal article
- research article
- Published by American Society for Microbiology in Applied and Environmental Microbiology
- Vol. 45 (3) , 974-979
- https://doi.org/10.1128/aem.45.3.974-979.1983
Abstract
The occurrence of pathogenic Naegleria fowleri in thermal discharges, recipient waters, and cooling towers of eight power plants located in western Pennsylvania was investigated for 2 years in conjunction with several environmental measurements. Pathogenic N. fowleri was detected in one cooling tower and in the discharge, receiving waters, or both of five of eight localities. The occurrence of this organism was related to elevated temperatures, but no significant correlation was found for other biological and chemical parameters. Laboratory experiments on the effect of pH on pathogenic N. fowleri documented 100% survival at a range from 2.1 to 8.15. Higher pH reduced or killed the amoebae. No case of human primary amoebic meningoencephalitis occurred during the study.This publication has 4 references indexed in Scilit:
- Isoenzyme patterns of pathogenic and non-pathogenic Naegleria spp. using agarose isoelectric focusing.1982
- Isolation of the etiological agent of primary amoebic meningoencephalitis from artifically heated watersApplied and Environmental Microbiology, 1977
- The effect of thermal pollution on the distribution ofNaegleria fowleriEpidemiology and Infection, 1975
- Acute Pyogenic Meningitis Probably Due to Acanthamoeba sp.: a Preliminary ReportBMJ, 1965