Measurements of pressure drop and heat transfer in turbulent pipe flows of particulate slurries
- 1 May 1988
- report
- Published by Office of Scientific and Technical Information (OSTI)
Abstract
Argonne National Laboratory (ANL), under sponsorhip of the US Department of Energy, Office of Buildings and Community Systems, has been conducting a comprehensive, long-range program to develop high- performance advanced energy transmission fluids for use in district heating and cooling (DHC) systems. The current study focuses on the development of phase-change slurries as advanced energy transmission fluids. The objectives are (1) to establish proof-of-concept of enhanced heat transfer by a slurry, with and without phase change, relative to heat transfer in a pure carrier liquid; (2) to investigate the effect of particle volumetric loading, size, and flow rate on the slurry pressure drip and heat transfer behavior with and without friction-reducing additives; and (3) to generate pressure drop and heat transfer data needed for the development and design of improved DHC systems. Two types of phase-change materials were used in the experiments: ice slush for cooling, and cross-linked, high- density polyethylene (X-HDPE) particles with diameters of 1/8 and 1/20 in. (3.2 and 1.3 mm) for heating. The friction-reducing additive used in the tests was Separan AP-272 at 65 wppm. This report describes the test facility, discusses the experimental procedures, and presents significant experimental results on flow and heat transfer characteristicsmore » of the non-melting slurry flows. 51 refs., 36 figs., 6 tabs. « lessKeywords