EMTP transient modeling of a distance relay and a comparison with EMTP laboratory testing
- 1 July 1993
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 8 (3) , 984-992
- https://doi.org/10.1109/61.252626
Abstract
A method to test the transient performance of a sampled-data relay is given. A model of one measuring unit of a digital relay is created on a personal computer. The simulations are compared with laboratory results obtained by applying digitally generated waveforms to the actual relay. Computer modeling of the digital relay is done within the models version of the Transient Analysis of Control System (TACS) subsection of the ElectroMagnetics Transient Program (EMTP). The input filter, analog-to-digital converter, Fourier fundamental frequency detector, and the relay measuring principle of one digital microprocessor-based relay are modeled. An actual 115 kV 150 mile long transmission line is simulated using the EMTP.Keywords
This publication has 6 references indexed in Scilit:
- RETEX (RElay Testing EXpert): an expert system for analysis of relay testing dataPublished by Institute of Electrical and Electronics Engineers (IEEE) ,2002
- A real time digital simulator for testing relaysIEEE Transactions on Power Delivery, 1992
- Discover relay design and application problems using pseudo-transient testsIEEE Transactions on Power Delivery, 1991
- 'MORGAT': a data processing program for testing transmission line protective relaysIEEE Transactions on Power Delivery, 1988
- Directional Characteristics of Distance Relay Mho Elements: Part I - A new Method of AnalysisIEEE Transactions on Power Apparatus and Systems, 1981
- Graphical Method for Estimating the Performance of Distance Relays During Faults and Power SwingsTransactions of the American Institute of Electrical Engineers, 1949