wall Superheat Excursions in the Boiling incipience of Dielectric Fluids
- 1 June 1988
- journal article
- research article
- Published by Taylor & Francis in Heat Transfer Engineering
- Vol. 9 (3) , 19-31
- https://doi.org/10.1080/01457638808939668
Abstract
Many of the candidate fluids for immersion cooling of microelectronic components possess both low surface tension and high gas solubility. As a consequence, ebullient heat transfer with such fluids is accompanied by nucleation anomalies and a frequently observed wall temperature overshoot. The difficulty in preventing this thermal excursion and in predicting its magnitude constrains the development of immersion cooling systems. This paper begins with a brief review of the mechanisms that may be responsible for delayed nucleation and examines the limited literature on incipience superheat excursions.Keywords
This publication has 9 references indexed in Scilit:
- Heat-transfer correlations for natural convection boilingPublished by Elsevier ,2003
- Transient boiling heat transfer from two different heat sources: Small diameter wire and thin film flat surface on a quartz substrateInternational Journal of Heat and Mass Transfer, 1984
- Corresponding States Correlations of the Spinodal and Homogeneous Nucleation LimitsJournal of Heat Transfer, 1982
- Homogeneous Nucleation and the Spinodal LineJournal of Heat Transfer, 1981
- The Evolution of Enhanced Surface Geometries for Nucleate BoilingHeat Transfer Engineering, 1981
- Corresponding States Correlations of the Extreme Liquid Superheat and Vapor SubcoolingJournal of Heat Transfer, 1978
- Liquid cooling of microelectronic devices by free and forced convectionMicroelectronics Reliability, 1972
- Multi-fluid Subdued Boiling; Theoretical Analysis of Multi-fluid Interface BubblesIBM Journal of Research and Development, 1971
- On the Nature and Location of Bubble Nuclei in Boiling from SurfacesJournal of Applied Physics, 1958