Arc Cooling and Short Line Fault Interruption
- 1 May 1971
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Apparatus and Systems
- Vol. PAS-90 (3) , 1094-1102
- https://doi.org/10.1109/tpas.1971.292873
Abstract
This paper covers the derivation of two sets of short line fault equations for the maximum rate of rise of recovery voltage (RRRV) characteristic of gas blast interrupters. The assumption that the electrical conductivity is proportional to the heat flux potential leads to a Cassie integral equation for post-arc current, a critical thermal time constant and the first set of RRRV equations. The assumption that the electrical conductivity varies exponentially with the heat flux potential leiads to the Mayr equation and the second set of RRRV equations. For both sets of equations it is shown that the maximum RRRV is (a) approximately proportional to the gas pressure; (b) proportional to the effective nozzle arc length at current zero and the number of series breaks; (c) proportional to temperature dependent coefficients which are functions of gas properties; and (d) inversely proportional to (dI/dt)m where m=3/2 and 1 for the "Cassie" and "Mayr" RRRV equations, respectively. These equations are complementary and serve as "first-order" limits on the interrupting capability of gas blast interrupters.Keywords
This publication has 4 references indexed in Scilit:
- Boundary Layer Analysis of an SF6 Circuit Breaker ArcIEEE Transactions on Power Apparatus and Systems, 1971
- Severe Rates of Rise of Recovery Voltage Associated with Transmission Line Short CircuitsTransactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems, 1957
- A Study of A-C Arc Behavior Near Current Zero by Means or Mathematical ModelsTransactions of the American Institute of Electrical Engineers, 1948
- Beiträge zur Theorie des statischen und des dynamischen LichtbogensElectrical Engineering, 1943