Comparative assessment of chlorine, heat, ozone, and UV light for killing Legionella pneumophila within a model plumbing system
- 1 February 1987
- journal article
- research article
- Published by American Society for Microbiology in Applied and Environmental Microbiology
- Vol. 53 (2) , 447-453
- https://doi.org/10.1128/aem.53.2.447-453.1987
Abstract
Nosocomial Legionnaires disease can be acquired by exposure to the organism from the hospital water distribution system. As a result, many hospitals have instituted eradication procedures, including hypercholorination and thermal eradication. We compared the efficacy of ozonation, UV light, hyperchlorination, and heat eradication using a model plumbing system constructed of copper piping, brass spigots, Plexiglas reservoir, electric hot water tank, and a pump. Legionella pneumophila was added to the system at 10(7) CFU/ml. Each method was tested under three conditions; (i) nonturbid water at 25 degrees C, (ii) turbid water at 25 degrees C, and (iii) nonturbid water at 43 degrees C. UV light and heat killed L. pneumophila most rapidly and required minimal maintenance. Both UV light and heat (60 degrees C) produced a 5 log kill in less than 1 h. In contrast, both chlorine and ozone required 5 h of exposure to produce a 5 log decrease. Neither turbidity nor the higher temperature of 43 degrees C impaired the efficacy of any of the disinfectant methods. Surprisingly, higher temperature enhanced the disinfecting efficacy of chlorine. However, higher temperature accelerated the decomposition of the chlorine residual such that an additional 120% volume of chlorine was required. All four methods proved efficacious in eradicating L. pneumophila from a model plumbing system.This publication has 20 references indexed in Scilit:
- Mode of transmission of Legionella pneumophila. A critical review.1986
- NOSOCOMIAL LEGIONELLOSIS IN SURGICAL PATIENTS WITH HEAD-AND-NECK CANCER: IMPLICATIONS FOR EPIDEMIOLOGICAL RESERVOIR AND MODE OF TRANSMISSIONThe Lancet, 1985
- Survial of Legionella pneumophila in a Model Hot Water Distribution SystemMicrobiology, 1984
- Heat eradication measures for control of nosocomial legionnaires' disease Implementation, education, and cost analysisAmerican Journal of Infection Control, 1984
- Susceptibility of Legionella pneumophila to chlorine in tap waterApplied and Environmental Microbiology, 1983
- SUBTYPES OF LEGIONELLA PNEUMOPHILA SEROGROUP 1 ASSOCIATED WITH DIFFERENT ATTACK RATESThe Lancet, 1983
- LEGIONELLACEAE IN THE HOSPITAL WATER-SUPPLYThe Lancet, 1983
- LEGIONELLA PNEUMOPHILA IN WATER PLUMBING SYSTEMSThe Lancet, 1982
- Ubiquitousness ofLegionella pneumophilain the Water Supply of a Hospital with Endemic Legionnaires' DiseaseNew England Journal of Medicine, 1982
- Pittsburgh Pneumonia Agent: Direct Isolation from Human Lung TissueThe Journal of Infectious Diseases, 1980