Power-factor compensation of thyristor-controlled single-phase load
- 1 January 1973
- journal article
- Published by Institution of Engineering and Technology (IET) in Proceedings of the Institution of Electrical Engineers
- Vol. 120 (2) , 245-246
- https://doi.org/10.1049/piee.1973.0052
Abstract
It is found that an effective way to obtain a, good power factor with a thyristor-controlled load is to use a parallel-connected uncontrolled resistive load of similar rating. The use of parallel-connected capacitance alone gives no significant degree of power-factor improvement, even when the capacitance is adjusted to the optimum value for each step of thyristor firing angle.Keywords