Abstract
A method of determining the standard deviation and critical flashover (CFO) of flashover probability data which utilizes simple graphical techniques to obtain estimates of the parameters is developed. Suggestions are made regarding testing procedures to optimize information gained with a given number of voltage applications.Keywords
This publication has 2 references indexed in Scilit:
- Full-Scale Tests for the Allegheny Power System 500-kV Tower-Insulation SystemIEEE Transactions on Power Apparatus and Systems, 1966
- The Determination of Switching Surge Withstand Voltages for EHV Insulation SystemsIEEE Transactions on Power Apparatus and Systems, 1964