Real Time Results with On-Line Network Equivalents for Control Center Applications
- 1 December 1981
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Apparatus and Systems
- Vol. PAS-100 (12) , 4830-4837
- https://doi.org/10.1109/tpas.1981.316445
Abstract
Extensive analysis and testing with real time data of the AEP system for various types of equivalencing techniques has been performed. It was found that for real time on-line applications the REI-type equivalents performed better than other equivalencing methods (Ward-type equivalents). It is shown that the equivalent updating procedure used for REI-type equivalents cannot be used for Ward-type equivalents. Ward-type equivalents which performed well for off-line planning applications and for some simulated real time applications did not work as well under realistic on-line conditions.Keywords
This publication has 6 references indexed in Scilit:
- On-Line Load Forecasting for Energy Control Center ApplicationIEEE Transactions on Power Apparatus and Systems, 1982
- Power Engineering Society 1981 Prize Paper Real-Time External System Equivalent for on-Line Contingency AnalysisIEEE Power Engineering Review, 1981
- Studies on Power System Load Flow EquivalencingIEEE Transactions on Power Apparatus and Systems, 1980
- Steady State Network Equivalents for Power System Planning ApplicationsIEEE Transactions on Power Apparatus and Systems, 1980
- Numerical Testing of Power System Load Flow EquivalentsIEEE Transactions on Power Apparatus and Systems, 1980
- Real-Time External Equivalents for Static Security AnalysisIEEE Transactions on Power Apparatus and Systems, 1979