Current Transformer and Relay Performance in the Presence of Geomagnetically-Induced Currents
- 1 March 1981
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Apparatus and Systems
- Vol. PAS-100 (3) , 1078-1088
- https://doi.org/10.1109/tpas.1981.316574
Abstract
Transient fluctuations in the earth's magnetic field are caused by solar flares or other solar phenomena. These geomagnetic field disturbances cause quasi-dc geomagnetically-induced currents (GIC) to enter a power system at grounded neutral points. The GIC is usually of sufficient magnitude to cause half-cycle saturation of large power transformers. GIC's in excess of 100 amperes have been measured in transformer neutrals, and GIC's of over 200 amps per phase can be expected on some autotransformers. This paper presents the results of studies investigating the effects of GIC upon current transformer and relay performance. The average CT flux density and CT error are examined in the presence of GIC. The effect of GIC upon CT remanence is also presented. The transient performance of the CT is studied to determine the reduced time-to-saturation from a combination of GIC and DC fault offset. Relay performance is considered in two categories (1) relay misoperation resulting from erroneous CT response, and (2) relay misoperation resulting from GIC interaction with large power transformers, notably differential protectionKeywords
This publication has 7 references indexed in Scilit:
- Harmonics and Switching Transients in the Presence of Geomagnetically-Induced CurrentsIEEE Transactions on Power Apparatus and Systems, 1981
- Load-Flow Studies in the Presence of Geomagnetically-Induced CurrentsIEEE Transactions on Power Apparatus and Systems, 1981
- Effects of direct currents in power transformers Part I. A general theoretical approachElectric Power Systems Research, 1978
- Outage of the L4 System and the Geomagnetic Disturbances of 4 August 1972Bell System Technical Journal, 1974
- Design Considerations in the Application of Current Transformers for Protective Relaying PurposesIEEE Transactions on Power Apparatus and Systems, 1973
- Control of Residual Flux in Current TransformersIEEE Transactions on Power Apparatus and Systems, 1973
- Digital Computer Solution of Electromagnetic Transients in Single-and Multiphase NetworksIEEE Transactions on Power Apparatus and Systems, 1969