Development of a New Type Fault Locator Using the One-Terminal Voltage and Current Data
- 1 August 1982
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Apparatus and Systems
- Vol. PAS-101 (8) , 2892-2898
- https://doi.org/10.1109/tpas.1982.317615
Abstract
A new type fault locator has been developed, that calculates the reactance of a faulty line, with a micro-processor, using the one-terminal voltage and current data of the transmission line. Errors caused by various factors such as load flow, fault resistance, and the unsymmetrical arrangement of the transmission line, are automatically corrected. The equipment is now under field test, and during the nine months of the field test, the equipment has operated satisfactorily.Keywords
This publication has 2 references indexed in Scilit:
- A New Algorithm of an Accurate Fault Location for EHV/UHV Transmission Lines: Part II - Laplace Transform MethodIEEE Transactions on Power Apparatus and Systems, 1982
- A New Alogorithm of an Accurate Fault Location for EHV/UHV Transmission Lines: Part I - Fourier Transformation MethodIEEE Transactions on Power Apparatus and Systems, 1981