Abstract
In 1981, sixteen cases of nosocomial legionellosis occurred among 456 patients admitted to a new hematology-oncology unit (35 per 1000 admissions). Monoclonal antibody typing and restriction endonuclease plasmid analysis identified a unique strain (09,04) of Legionella pneumophila serogroup 1 isolated from both patients and water outlets. Continuous hyperchlorination of the hot and cold water began in January 1982, and chlorine levels of 3 to 5 mg/L have been maintained most recently. Water samples have been consistently negative for Legionella for more than five years. Four sporadic cases of nosocomial legionellosis have occured in the hematology-oncology unit during the same period (one per 1000 admissions) associated with a different strain of L. pneumophila serogroup 1 (09,00). The environmental reservoir(s) of L. pneumophila serogroup 1 in these cases has not been identified. Levels of trihalomethanes (potential carcinogens) were high (> 100 .mu.g/L) when chlorine levels of hot water exceeded 4 mg/L. Some corrosion damage to the water distribution system has occurred: the average number of leaks per month increased steadily from zero in 1982 to 5.2 in 1986. The chlorinator installation costs were $75,800, and annual operation expenses were $12,500. Continuous hyperchlorination is a promising but still experimental technique for control of nosocomial legionellosis. In our experience, epidemic disease has been controlled, but sporadic cases have continued to occur.