Switching Capacitive Kilovolt-Amperes with Power Circuit Breakers [includes discussion]
- 1 January 1952
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in Transactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems
- Vol. 71 (1) , 188-200
- https://doi.org/10.1109/aieepas.1952.4498460
Abstract
Although power circuit breakers are designed primarily to interrupt heavy inductive short-circuit currents, system growth in recent years has produced a greatly increased requirement of interrupting relatively lighter currents which are associated with the switching of capacitive kilovolt-amperes. This capacitive kilovolt-ampere requirement has manifested itself in long-distance high-voltage transmission lines, in relatively long high-voltage cables, and in large size shunt capacitor banks which are becoming a common fundamental unit in system design and operation.1-3 There is not necessarily a relationship between the ability of a circuit breaker to interrupt short circuit currents and its ability to switch capacitance currents. It is widely recognized that high-frequency voltage and current oscillations may be produced which, if uncontrolled, may result in damage to apparatus or system outages. In general, the problem is the severity of the system disturbances produced by the switching operation, either opening or closing, rather than the failure of the circuit breaker to interrupt the current or to close the circuit. It is the purpose of this paper to present: 1. Typical circuit breaker performance in switching capacitive kilovolt-amperes. 2. Circuit behavior and circuit breaker performance considerations from test laboratory and transient analyzer studies. 3. Criteria of acceptable circuit breaker performance in capacitive switching.Keywords
This publication has 7 references indexed in Scilit:
- A New 69-Kv Air Blast Circuit BreakerTransactions of the American Institute of Electrical Engineers, 1951
- Switching High-Voltage Shunt Capacitor BanksTransactions of the American Institute of Electrical Engineers, 1951
- Unusual Performance of Standard 230-Kv Impulse and Tank-Type Oil Circuit Breakers on Field TestsTransactions of the American Institute of Electrical Engineers, 1948
- Resistors for 138-Kv Cable SwitchingTransactions of the American Institute of Electrical Engineers, 1947
- Switching Overvoltage Hazard Eliminated in High-Voltage Oil Circuit BreakersTransactions of the American Institute of Electrical Engineers, 1943
- Tets and Analysis of Circuit-Breaker Performance When Switching Large Capacitor BanksTransactions of the American Institute of Electrical Engineers, 1942
- Analysis of Factors which Influence the Application, Operation, and Design of Shunt-Capacitor Equipments Switched in Large BanksTransactions of the American Institute of Electrical Engineers, 1940