Relationship Between Corona and Radio Influence on Transmission Lines, Laboratory Studies I-Point and Conductor Corona
- 1 April 1957
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in Transactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems
- Vol. 76 (3) , 530-538
- https://doi.org/10.1109/aieepas.1957.4499603
Abstract
1. When a quasipeak-type RN meter is used for the measurement of a corona noise, it is advisable to calibrate the meter with a pulse generator. 2. A procedure of calibration and a calibration chart are given. Consistent readings have been obtained for all the meters so calibrated. 3. Within the range of measurements the RN meter readings are linearly proportional to the voltage of square pulses and to the pulse width between 2 and 200 millimicroseconds above which the increase is no longer linear. 4. A given RI level can result from a variety of corona patterns characterized by the number, magnitude polarity, width, and distribution of pulses. These characteristics can sometimes be used to differentiate between the types of corona noise. 5. A good correlation between corona pulses and RI values can be obtained for a given setup if the repetition rate is known for each group of pulses of equal magnitude 6. Sudden jumps of RI were observed when an electrode with sharp points was subjected to a critical voltage. The instability was associated with the onset of corona pulses in the positive half cycle of the applied voltage. 7. Since moist insulating points cause much higher corona pulses and RI than metal points, it is possible that vegetation deposits on transmission-line conductors are more liable to cause RI than are surface imperfections. 8.Keywords
This publication has 9 references indexed in Scilit:
- An Analysis of the Radio-Interference Characteristics of Bundled Conductors [includes discussion]Transactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems, 1956
- The Calculation of the Radio Interference Level of Transmission Lines Caused by Corona Discharges [includes discussion]Transactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems, 1956
- The quasi-peak voltmeterTransactions of the American Institute of Electrical Engineers, Part I: Communication and Electronics, 1954
- The two-dimensional magnetic or electric field above and below an infinite corrugated sheetBritish Journal of Applied Physics, 1953
- Radio Influence Tests in Field and Laboratory - 500-Kv Test Project of the American Gas and Electric CompanyTransactions of the American Institute of Electrical Engineers, 1951
- Progress Report on Tidd 500-Kv Test Project of the American Gas and Electric Company---Corona, Radio Influence, and Other FactorsTransactions of the American Institute of Electrical Engineers, 1950
- Radio Influence from High-Voltage CoronaTransactions of the American Institute of Electrical Engineers, 1949
- Radio-Noise Influence of 230-Kv LinesTransactions of the American Institute of Electrical Engineers, 1947
- A Study of Wave Shapes for Radio-Noise-Meter CalibrationsTransactions of the American Institute of Electrical Engineers, 1945