Rating of General-Purpose Induction Motors
- 1 September 1939
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in Transactions of the American Institute of Electrical Engineers
- Vol. 58 (9) , 445-459
- https://doi.org/10.1109/T-AIEE.1939.5057986
Abstract
This paper reviews principles of rating of general-purpose a-c motors, particularly in relation to overload torque and temperature limits. The overload capacity of an electric motor is limited, first, by its stalling, or breakdown torque, and, second, by its operating temperature. The breakdown torque, analogous to the stalling torque of a gas engine, is roughly proportional to the motor size and the square of its magnetic flux density. The temperature limitation is exactly analogous to the temperature limit of a transformer, the useful life of the insulation being reduced exponentially as the temperature is raised. The increased variety of motor uses in recent years, especially for automatic operation of refrigerator compressors, air conditioning, pumps, and other mechanical devices, has led to more exact methods of application, utilizing motor overload capacity and matching torque characteristics to the driven equipment. Under this economic pressure, motor overload capacities have been increased over the requirements of present standards, and small motors are now commonly used on intermittent overloads far beyond their continuous ratings. It is proposed, therefore, that American standards be revised to provide for increased values of breakdown torque and service factor in the smaller motor ratings, and that permissible intermittent duty cycles be defined, enabling the full economic life of the motor to be utilized.Keywords
This publication has 5 references indexed in Scilit:
- Duty Cycles and Motor RatingTransactions of the American Institute of Electrical Engineers, 1939
- Temperature Aging Characteristics of Class A InsulationTransactions of the American Institute of Electrical Engineers, 1939
- Determination of Temperture Rise of Induction MotorsTransactions of the American Institute of Electrical Engineers, 1939
- Temperature limits for short-time overloads for oil-insulated neutral grounding reactors and transformersElectrical Engineering, 1938
- Loading Transformers By TemperatureTransactions of the American Institute of Electrical Engineers, 1930