Extending Cooling Tower thermal Performance Prediction Using a Liquid-Side Film Resistance Model
- 1 January 1991
- journal article
- research article
- Published by Taylor & Francis in Heat Transfer Engineering
- Vol. 12 (3) , 19-30
- https://doi.org/10.1080/01457639108939753
Abstract
Current models used to analyze the thermal performance of cooling towers assume that the air/water interfacial temperature is equivalent to the bulk temperature of the water, or, in other words, that the liquid-side film resistance is negligible. This assumption is a possible source of the dependence on inlet hot water temperatures found in cooling tower packing heat and mass transfer correlations derived from these models. For applications in which the water temperatures exceed the limits of experimental data used in developing such correlations, a resulting high level of uncertainty exists. This article describes a method by which one-dimensional cooling tower model equations can be corrected to account for liquid-side film resistance. The use of these corrected equations in the development of temperature-independent heat and mass transfer correlations for tower packings is also described.Keywords
This publication has 1 reference indexed in Scilit:
- Design of Cooling Towers by the Effectiveness-NTU MethodJournal of Heat Transfer, 1989