Second Law Analysis of Desiccant Cooling Systems
- 1 August 1982
- journal article
- Published by ASME International in Journal of Solar Energy Engineering
- Vol. 104 (3) , 229-236
- https://doi.org/10.1115/1.3266307
Abstract
A second law analysis of constant pressure open cycle cooling systems was performed in order to assess the potential performance of desiccant cooling systems. The results yield upper bounds which are independent of the nature of the desiccant. Calculations carried out for a wide range of operating conditions show that the performance of these open cycle systems strongly depends on the humidity ratio. For ARI conditions, the reversible COP is about 4.66, and it approaches infinity at very low outdoor humidity ratios.Keywords