Location of Series Capacitors in High-Voltage Transmission Systems [includes discussion]
- 1 December 1953
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in Transactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems
- Vol. 72 (6) , 1140-1151
- https://doi.org/10.1109/aieepas.1953.4498750
Abstract
Over-all system economy can be improved by means used specifically to increase the power limits of high-voltage, large-conductored transmission lines.1-24 Important methods for increasing the stability limits of high-voltage transmission systems are: 1. Intermediate switching stations, with and without series capacitor compensation. 2. Intermediate systems. 3. Automatic circuit reclosing. 4. Switched shunt capacitors and reactors. 5. Generator excitation systems. This paper reviews and compares four possible methods of applying series capacitors, together with intermediate switching stations for improving the transient stability limit of high-voltage systems. The function of intermediate switching stations to improve the stability limits of transmission lines is primarily that of removing transmission line faults by disconnecting a smaller line section with a correspondingly smaller shock than if intermediate switching stations were not used. Detailed studies of intermediate switching stations have been previously reported24 which indicate that they can be economical for lines as short as 50 miles. Series capacitors reduce the over-all line reactance, and hence allow a larger stable transfer of power. Series capacitors can also be applied to obtain better load division21,22 on parallel lines having different conductor resistances and/- or different lengths, although series capacitors applied for this purpose show only marginal economic benefits. In general, series capacitors appear to be economical for increasing the stability limit of lines about 200 miles or longer. There has been, however, some divergence of opinion as to the most economical location for the series capacitors in the transmission system.Keywords
This publication has 15 references indexed in Scilit:
- Economic Aspects of Series Capacitors in High-Voltage TransmissionTransactions of the American Institute of Electrical Engineers, 1951
- A 24,000-Kilovar Series Capacitor in a 230-Kv Transmission LineTransactions of the American Institute of Electrical Engineers, 1951
- The proposed Colorado River developmentsElectrical Engineering, 1947
- Characteristics of a 400-Mile 230-Kv Series-Capacitor-Compensated Transmission SystemTransactions of the American Institute of Electrical Engineers, 1946
- Steady-State Stability or Synchronous Machines as Affected by Voltage-Regulator CharacteristicsTransactions of the American Institute of Electrical Engineers, 1944
- Steady-State and Transient-Stability Analysis of Series Capacitors in Long Transmission LinesTransactions of the American Institute of Electrical Engineers, 1943
- Series Capacitors for Transmission CircuitsTransactions of the American Institute of Electrical Engineers, 1942
- Analysis of the Application of High-Speed Reclosing Breakers to Transmission SystemsTransactions of the American Institute of Electrical Engineers, 1942
- Stability Limitations of Long-Distance A-C Power-Transmission SystemsTransactions of the American Institute of Electrical Engineers, 1941
- Five Years' Experience with Ultrahigh- Speed Reclosing of High-Voltage Transmission LinesTransactions of the American Institute of Electrical Engineers, 1941