Heat Losses in Isolated-Phase Bus Enclosures
- 1 June 1963
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Apparatus and Systems
- Vol. 82 (66) , 308-318
- https://doi.org/10.1109/tpas.1963.291358
Abstract
Formulas are given for the evaluation of heat losses in the enclosures of isolated-phase bus installations in flat configuration. Middle-and outside-phase losses in open-circuited and electrically bonded enclosures are considered. Middle-phase open-circuited enclosure losses estimated by the proposed formula are compared with loss values inferred from temperature data on 40 heat runs involving a wide range of design parameters. The comparison shows acceptable agreement.Keywords
This publication has 4 references indexed in Scilit:
- An Analog Method for Determining Losses in Isolated-Phase Bus EnclosuresIEEE Transactions on Power Apparatus and Systems, 1963
- Isolated-Phase Metal-Enclosed Conductors for Large Electric GeneratorsTransactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems, 1962
- Minimizing the Magnetic Field Surrounding Isolated-Phase Bus by Electrically Continuous EnclosuresTransactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems, 1962