A Comparative Study Of Discomfort Caused By Indoor Air Pollution, Thermal Load And Noisec
- 1 December 1993
- journal article
- Published by Hindawi Limited in Indoor Air
- Vol. 3 (4) , 255-262
- https://doi.org/10.1111/j.1600-0668.1993.00006.x
Abstract
The relative importance of sensory air pollution, thermal load and noise was studied under controlled conditions in two identical environmental chambers. In one chamber subjects were exposed to various levels of either thermal load or poor indoor air quality. For each condition tested in this chamber, the subjects were exposed to a number of noise levels in an adjacent chamber with neutral thermal conditions and good indoor air quality in order to determine a noise level causing the same degree of discomfort. A total of 68 comparisons of the conditions in the two chambers were made by the same group of 16 subjects after one-minute exposure in each chamber. In the operative temperature range of 23–29°C, a 1°C change in operative temperature was found to have the same effect on human comfort as a change in perceived air quality of 2.4 decipol or a change in noise level of 3.9 dB. For levels of perceived air quality up to 10 decipol, a 1 -decipol change in perceived air quality had the same effect on human comfort as a change in noise level of 1.2 dB. A relationship between traffic noise level and percentage dissatisfied was establishedKeywords
This publication has 5 references indexed in Scilit:
- Influence of session length on judged annoyanceJournal of Sound and Vibration, 1991
- Introduction of the olf and the decipol units to quantify air pollution perceived by humans indoors and outdoorsEnergy and Buildings, 1988
- Combined Effects of Heat and Noise on Human Performance: A ReviewAihaj Journal, 1985
- Effects of Noise and Heat Stress on Primary and Subsidiary Task PerformanceHuman Factors: The Journal of the Human Factors and Ergonomics Society, 1978
- Can Colour and Noise Influence Man's Thermal Comfort?Ergonomics, 1977