Harmonics And Reactive Power From Line-Commutated Inverters In Propposed Photovoltaic Subdivision
- 1 September 1983
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Apparatus and Systems
- Vol. PAS-102 (9) , 3205-3211
- https://doi.org/10.1109/TPAS.1983.318130
Abstract
This paper describes how one hundred 6.6 kW line-commutated inverters in a proposed photovoltaic subdivision will affect the 10 MVA distribution feeder to which the inverters are connected. Voltage distortion and reactive power correction were studied using a special simulation computer program. The worst-case level of voltage total harmonic distortion is 6.2%, and by setting capacitor switching practices carefully it should be possible to keep voltage THD around 2-3%. The harmonic distortion is greatly affected by the placement of capacitors on the system.Keywords