A Sequential Phase Energization Technique for Transformer Inrush Current Reduction— Part I: Simulation and Experimental Results
- 4 April 2005
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 20 (2) , 943-949
- https://doi.org/10.1109/tpwrd.2004.843467
Abstract
This paper presents a new, simple and low cost method to reduce inrush currents caused by transformer energization. The method uses a grounding resistor connected at a transformer neutral point. By energizing each phase of the transformer in sequence, the neutral resistor behaves as a series-inserted resistor and thereby significantly reduces the energization inrush currents. The proposed method has been tested by computer simulation and laboratory experiments. Both results show that the method has a performance similar to that of the resistor pre-insertion scheme. The proposed method is much less expensive, however, since there is only one resistor involved and the resistor carries only a small neutral current in steady-state.Keywords
This publication has 5 references indexed in Scilit:
- A new technique to mitigate inrush current caused by transformer energizationPublished by Institute of Electrical and Electronics Engineers (IEEE) ,2003
- Analysis of transformer inrush transients in offshore electrical systemsIEE Proceedings - Generation, Transmission and Distribution, 1999
- A contribution to the modeling of three phase transformers using reluctancesIEEE Transactions on Magnetics, 1996
- The calculation of inrush current in three-phase transformersIEE Proceedings B Electric Power Applications, 1986