A New Control Method for Multiterminal HVDC Transmission Without Fast Communications Systems
- 1 May 1983
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Apparatus and Systems
- Vol. PAS-102 (5) , 1140-1150
- https://doi.org/10.1109/TPAS.1983.318054
Abstract
A new control scheme (the 2-ACR method) for parallel multiterminal HVDC systems is proposed. The method does not require fast communication systems. Any terminal can be disconnected or connected to the system without power re-coordination, since a new stable operating point can be always determined automatically by control actions of each converter with two automatic current regulators and one constant voltage controller. A light duty dc circuit breaker can disconnect a fault line, and the remaining terminals can restore transmission power as fast as possible. The excellent performance of the proposed scheme has been demonstrated by digital simulations using EMTP.Keywords