Investigation of Interrupting Performance of Puffer Type Gas Blast Circuit Breaker Under Various Nozzle Clogging Conditions
- 1 November 1980
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Apparatus and Systems
- Vol. PAS-99 (6) , 2086-2093
- https://doi.org/10.1109/TPAS.1980.319850
Abstract
The interrupting ability of a puffer type Gas Blast Circuit Breaker (GCB) was investigated under various nozzle clogging conditions. A model puffer type GCB was used in the interrupting experiments, in which nozzle diameter, nozzle geometry and current wave form were varied. The following results were obtained from the experiments, 1 At a nozzle current density of 2.5-5.5kA/cm2, the low puffer pressure makes it possible to interrupt a current with a large dI/dt. 2 An increase of base gas pressure effectively contributes to improving interrupting ability. 3 The puffer chamber pressure rise which is caused by excess nozzle clogging does not improve interrupting ability.Keywords
This publication has 4 references indexed in Scilit:
- Investigation of Interrupting Performance of Puffer Type Gas Blast Circuit Breaker Under Various Nozzle Clogging ConditionsIEEE Transactions on Power Apparatus and Systems, 1980
- A Method and Applications of a Theoretical Calculation for on-load Pressure Rises in Puffer Type Gas Circuit BreakersIEEE Transactions on Power Apparatus and Systems, 1979
- Estimation and Performance Investigation on SLF Interrupting Ability of Puffer-Type Gas Circuit BreakerIEEE Transactions on Power Apparatus and Systems, 1979
- Investigation of dynamic nozzle parameters for various nozzle geometries and test conditions of an experimental half-size SF6puffer breakerIEEE Transactions on Power Apparatus and Systems, 1977