Versatile load flow method for multiterminal HVDC systems
- 1 May 1977
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Apparatus and Systems
- Vol. 96 (3) , 925-933
- https://doi.org/10.1109/t-pas.1977.32405
Abstract
Any configuration of multiterminal HVdc system is accommodated in a generalized Newton dc load-flow program. It readily interfaces with any ac load flow program. Pract ical operating requirements have been given particular attention to permit aspects such as converter transformer tap-limits, pole and bipolar dc outages, emergency pole-paralleling and detailed control and scheduling strategies. Examples are provided of typical solutions incorporating realistic dc and ac systems, and accomplished in conjunction with an established modern ac load flow program.Keywords
This publication has 3 references indexed in Scilit:
- The analysis of electrified ground transportation networksIEEE Transactions on Power Apparatus and Systems, 1977
- The control and performance of a series connected multiterminal HVDC transmission systemIEEE Transactions on Power Apparatus and Systems, 1975
- Fast Decoupled Load FlowIEEE Transactions on Power Apparatus and Systems, 1974